manualshive.com logo in svg
background image

Variatore di frequenza
Frequency converter
Variateur de fréquence
Variador de frecuencia
Frequenzumwandler
Регулятор частоты

EASYMAT

ISTRUZIONI ORIGINALI PER L’USO

P 444.06  I

Pagina 

2

Italiano

ORIGINAL OPERATING INSTRUCTIONS

444.06

GB

Page 

16

English

INSTRUCTIONS ORIGINALES POUR L’UTILISATION

444.06

F

Page 

30 Français

INSTRUCCIONES ORIGINALES DE USO

444.06

E

Página 

44 Español

ORIGINAL BETRIEBSANLEITUNG

P

444.06

D

Seite

58 Deutsch

ОРИГИНАЛЬНЫЕ ИНСТРУКЦИИ ПО ЭКСПЛУАТАЦИИ

P

444.06

RU

ëÚ‡Ìˈ‡

72

êÛÒÒÍËÈ

istr_P444_06_Easymat_ita_gb_F_E_D_r:istr_P444  29/08/14  15.49  Pagina 1

Содержание EASYMAT 5MM

Страница 1: ...RUZIONI ORIGINALI PER L USO P 444 06 I Pagina 2 Italiano ORIGINAL OPERATING INSTRUCTIONS P 444 06 GB Page 16 English INSTRUCTIONS ORIGINALES POUR L UTILISATION P 444 06 F Page 30 Fran ais INSTRUCCIONE...

Страница 2: ...on 8 Dry running protection 9 Parameters 9 1 Parameters of pump status 9 2 Programming parameters 10 Programming 10 1 PASSWORD Insertion 11 Parameters to check when starting up the unit 11 1 Vessel pr...

Страница 3: ...quency of the pump being controlled Operating at a frequency higher than the allowable frequency can cause higher current absorption and damage to the device If it is necessary to remove the frequency...

Страница 4: ...g protection tank fill float switch safety pressure switch Analogue inputs pressure transducer 4 20 mA Digital outputs general alarm the display shows the type of alarm see paragraphs 7 6 and 9 3 Conn...

Страница 5: ...er 20s of system inactivity 5 3 3 Operating icons Constant pressure mode The system keeps the pressure constant when the quantity of water requested by the user changes Fixed speed mode The system wor...

Страница 6: ...mum section of 2 5mm2 We also advise the use of insulated pin terminals Bad connections may damage the electronic circuit 7 1 Power supply line Power supply line must comply with the provisions under...

Страница 7: ...g the instructions under paragraph 7 The power supply must comply the provisions of the paragraph 4 5 The connection with the power supply must be made with interpositions of magnetothermal bipolar sw...

Страница 8: ...ecommended to switch off and switch on all the frequency converter This configuration define an address for each frequency converter if not correctly configured cascade mode will not work properly Pre...

Страница 9: ...arameters are displayed Example 9 2 Programming parameters To display the programming parameters select menu Will be displayed progressively UP User settings these are the basis settings that user can...

Страница 10: ...P04 Time before stop s 30 AP05 Dry run time s 10 AP06 First dry run time s 60 AP07 Dry run pressure bar 1 5 AP08 System dynamic 3 1 fast dynamic 5 slow dynamic AP09 Cascade mode oFF oFF UU cascade mod...

Страница 11: ...fault Not connected cable broken connection pressure transducer spoiled Er03 Blockage due to low supply voltage Supply voltage lower than 190V The system automatically restart when the clamp voltage...

Страница 12: ...nter the next number start blinking If the password is correct you can enter on the MENU if the password is wrong the first number restart blinking To exit the program push menu until you arrive on th...

Страница 13: ...the pump by selecting stop as priming has not been carried out correctly and the pump is idling Re prime the pump and repeat the starting up procedure 12 1 Inversion of the direction of rotation To c...

Страница 14: ...ction Converter failure 5 Watt flashing red light plus 75 dB 3600 Hz acoustic alarm for use in areas of loud noise positioned in such a way as to be visible from a distance The control panel is fitted...

Страница 15: ...29 Modifica parametro Change parameter Changement de param tre Cambio de par metros Parameterwert ndern...

Страница 16: ...4 1 4 93 414 2 4 93 414 3 Max 4 5 mm 90 20 Schemi collegamento elettrico Electrical connection scheme Sch mas du branchement lectrique Esquemas de conexi n el ctrica Schemata der elektrischen Anschl s...

Страница 17: ...91 4 93 414 6 4 93 414 5 4 93 414 4...

Страница 18: ...92 4 93 414 5 4 93 414 5 4 93 414 5...

Страница 19: ...stallationsschema der Pumpe 22 1 Schemi installazione ad 1 pompa One pump installation scheme Sch mas de l installation 1 pompe Esquema de instalaci n a 1 bomba Installationsschema mit 1 Pumpe 1 21 Sc...

Страница 20: ...22 2 Schemi installazione a 2 pompe Two pump installation scheme Sch mas de l installation 2 pompes Esquema de instalaci n a 2 bombas Installationsschema mit 2 Pumpen 2 4 93 412 4 94...

Страница 21: ...tions des Directives 2004 108 CE 2006 95 CE et des normes harmonis es correspondantes CE EN 55014 1 CE EN 55022 CE EN 61000 3 3 CE EN 61000 4 2 CE EN 61000 4 3 CE EN 61000 4 4 CE EN 61000 4 5 CE EN 61...

Страница 22: ...Montorso Vicentino Vicenza Italia Tel 39 0444 476476 Fax 39 0444 476477 E mail info calpeda it www calpeda it RoHS P 444 06 Con riserva di modifiche Changes reserved Modifications r serv es Con reser...

Отзывы: