SD710 Series Servo User Manual Chapter 9 Parameter description
94
Pn806
Pr command communication parameters (single segment
operation)
О
Communication
address: 0x0806
Factory value:
10000
Setting range: 0 ~ 65535
Unit: N/A
Control mode.
□
P
Parameter
Description
①
DI terminal switching mode is valid, input 1 ~ 15 can trigger the corresponding Pr path, input
1000 can force the end of the current operation mode.
②
In position mode, enter 0 to trigger home return, and enter 1000 to force the end of home return.
Pn810
PR path 1 control word L
О
Communication
address: 0x0810
Factory value: 0x0000
Setting range: 0x0000~0x0121
Unit: N/A
Control mode.
□
P
PR Type (TYPE)
0
Positioning control
1
Fixed speed control
Type of positioning control
0
Positioning control as incremental position
1
Positioning control as absolute position
2
Positioning control as relative position
Fixed speed control unit
0
Speed units are 0.1 rpm
1
Speed in PPS
Reserved parameters (do not use)
Pn811
PR path 1 control word H
О
Communication
address: 0x0811
Factory value: 0x0000
Setting range: 0x0000
~
0x7777
Unit: N/A
Control mode.
□
P
3rd 2nd 1st 0th
u
X
Y
Z
W