SD710 Series Servo Drive User's Manual Chapter 7 Auxiliary Functions
4
assist
meri
torious
d
eed
or
service
capab
le
7.3 Clearing alarm records (Fn001)
This function is used to clear the alarm record of the Servo Drive. Alarm records generated by the Servo Drive Unit cannot
be cleared even if an alarm reset is performed or the main circuit power to the Servo Unit is disconnected. Only use this
auxiliary function to clear the relevant records.
The basic setup procedure is shown below.
Steps
Panel display
Keys used
Operations
1
Press MODE/SET to select the auxiliary function. Adjust
by pressing UP or DOWN until Fn000 is displayed.
2
Adjust by pressing UP or DOWN until Fn001 is displayed.
3
Press the DATA/SHIFT key for about 1 second, then the
display will be as shown on the left.
4
Press the Up key to set the current display value to
"trCL2".
(blinking)
Press the MODE key to clear the fault record, and when
the fault record is cleared, "donE" flashes and returns to
the display on the left. When the display is not "trCL2",
press the "MODE" key, then the display will show "no-op",
which means the writing operation is prohibited.
5
-
After displaying donE, the status display of "trCL2" is
returned.
6
Press the DATA/SHIFT key for about 1 second to return to
the Fn006 display.
CAUTION
● Before clearing the alarm message, make sure that the parameter write ban function (Fn010) is
not
set to "Prohibit writing"
.