SD710 Series Servo Drive User's Manual Chapter 7 Auxiliary Functions
3
assist
meri
torious
d
eed
or
service
capab
le
7.2 Historical fault information search (Fn000)
The Servo Drive has a fault traceability display that can retroactively display up to ten alarms that have been generated.
The traceability contains.
①
The code when alarms.
②
The time when alarms.
The time when an alarm occurs is measured in 100ms units for the duration of time after the control power is turned on.
If it is operated 24 hours a day, 365 days a year, it can be measured continuously for about 13 years.
Example of time display when alarms.
When 72000 is displayed, 72000 x 100 [ms] = 7200 [s] = 120 [min] = 2 [h].
The procedure is shown below.
Steps
Panel display
Keys used
Operations
1
Press MODE/SET to select the auxiliary function. Adjust
by pressing UP or DOWN until Fn000 is displayed.
2
Pressing the DATA/SHIFT key for about 1 second
displays the latest alert, as shown on the left picture.
3
Each press of the DOWN key displays an old alarm
backwards; each press of the UP key displays a new
alarm backwards. The larger the number in the left end
digit, the older the alarm displayed.
4
Pressing the DATA/SHIFT key displays the last 4 digits
of the time when the fault occurred
5
Pressing the DATA/SHIFT key displays the middle 4
digits of the time when the fault occurred
6
Pressing the DATA/SHIFT key displays the first 2 digits
of the time when the fault occurred
7
Pressing the DATA/SHIFT key returns to the display of
the alarm number
8
Press MODE/SET to return to the Fn000 display
CAUTION
●
When the same alarm occurs consecutively, it is not saved if the interval between the occurrence of
alarms is less than one hour, otherwise it will be saved.
●
When no alarms
, "□." is displayed on the panel operator.
----".
●
Alarm logging can be cleared by "Clear Alarm Logging (Fn001)". Even if you perform an alarm
reset or Disconnecting the main circuit power to the servo unit also does not clear the alarm log.
MODE/SET
Data/
MODE/SET
Data/
MODE/SET
Data/
MODE/SET
Data/
MODE/SET
Data/
MODE/SET
Data/
MODE/SET
Data/
MODE/SET
Data/
!
Check the content from the alarm list
Sequence number when alarms