SD710 Series Servo Drive User Manual Chapter 5 Commissioning and Operation
44
counterclockwise (CCW)
clockwise (CW)
Pn277.X=0
Pn277.X=1
5.7.4 Steps for use
Step 1: Set the correct upper limit for the number of rotations (Pn276) according to the actual machine conditions.
Step 2: Set the direction selection (Pn277.X) when the upper limit of rotational turns is turned on.
Step 3: Use the auxiliary function Fn006 or the upper unit to clear the multi-turn value of the absolute encoder.
Precautions
●
This function is only valid when using absolute encoders.
●
Set the direction of rotation of the motor correctly, and make sure that the actual direction of motor operation
is the same as the direction set for the motor, otherwise the ER.840 alarm will be generated.
!