7.5 User parameter reset (Fn003)
This function is used when restoring the parameters to their factory settings.
CAUTION
●
Parameter set value initialization must be executed in the servo OFF state, and cannot be
executed in the servo ON state.
●
In order for the setting to take effect, the power of the servo unit must be turned on after operation.
The basic setup procedure is shown below.
Steps
Panel display
Keys used
Operations
1
Press MODE/SET to select the auxiliary function. Adjust by
pressing UP or DOWN until Fn000 is displayed.
2
Adjust by pressing UP or DOWN until Fn003 is displayed.
3
Press the DATA/SHIFT key for about 1 second, then the
display will be as shown on the left picture.
4
Press and hold the UP key until "P.Int2" is displayed.
5
(blinking)
Press MODE/SET to restore the user parameters to their
defaults. After setting is complete, donE flashes for about 1
second.
When the "MODE" key is pressed while "P.Int2" is not
displayed, the "no-op" prohibition sign is displayed.
6
-
When donE is displayed, the status display of "P.Int2" is
returned.
7
Press the DATA/SHIFT key for about 1 second to return to
the display of Fn003.
CAUTION
●
After the initialization of the parameter setting is completed, the power of the servo unit needs to
be turned on again.
!