TC1784
General Purpose Timer Array (GPTA
®
v5)
User´s Manual
21-44
V1.1, 2011-05
GPTA
®
v5, V1.14
Figure 21-30 Observation and Comparator Windows (timer is a power of 2)
The scalable and signed greater/equal comparator scheme leads to a limitation that
must be considered when programming the GPTA
®
v5 Module. If the timer range is not
a power of 2, the comparator window (always a power of 2) will no longer match the timer
period. This will impact the observation window as described in the following paragraph.
Observation window for reloaded timers (period is not a power of 2)
In that case, the comparator window must exceed the timer period. The user must find
the comparator window (by selecting the scale factor k) which fits best the timer period.
The following equation must apply:
2
k
< Period
≤
2
×
2
k
(21.1)
show that one part of the comparator window must be
discarded in order to avoid inconsistency, resulting in the observation window.
MCT05939
Before
After
T
Comparator Window (= 2 × 2
k
)
Observation Window (= Period)