19 - 32
19.6 Setting of Serial Multi-Drop Connection Unit
(3) Details on the word device assignment contents
(a)
Control signal 1-1
< 10 second cycle flicker signal
*1
>
By the repetition of turning ON/OFF every 5 seconds, the connection between GT01-RS4-M and the PLC can be
confirmed on the PLC side.
When no repetition of this ON/OFF is observed, GT01-RS4-M is not connected to the PLC.
*1
When writing or clearing data on the program area from the personal computer to the PLC using FA transparent function, flicker of
the signal as shown above may be temporarily stopped.
(b)
Station information notification signal
*1
This signal notifies the status of the slave station (GOT) which is connected to the master station (GT01-RS4-M).
Only the bit corresponding to the number of connected slave station (GOT) is turned ON and other bits are
turned OFF.
• 1: Connected
• 0: Unconnected (Including communication error status)
*1
When the communication between GT01-RS4-M and the PLC becomes faulty, the station information notification signal is not
updated.
(c)
Slave station control signal
This signal controls slave stations which are not updated by the master station.
Usually, the master station accesses all stations (up to 16 stations). In addition, if stations are temporarily in
communication error due to a power disconnection or screen data transfer during the steady operation, the
automatic recovery of the station is executed for one station per ten seconds. Therefore, the automatic recovery
may take maximum 2 minutes and 30 seconds.
Using this control signal, the number of slave stations to be monitored by the master station can be reduced to
the actual number of slave stations to be used by a user. This makes the automatic recovery processing smooth.
If an error occurs in only one station, the time for the station to recover automatically can be reduced within 10
seconds.
When the bits are off and the master station and the slave stations are in communication, the communication
with the corresponding slave stations is disconnected if the above corresponding bits are turned on.
Bit position
Description
bit0
10 second cycle flicker signal
bit1 to 15
(Reserve)
bit15
bit14
..................
bit2
bit1
bit0
Station
No. 15
Station
No. 14
..................
Station
No. 2
Station
No. 1
Station
No. 0
Device value
Action
0
The master station accesses all the slave stations (station 0 to 15). When the multi-drop system information is not used,
the operation is the same.
Other than 0
Turning on the bit corresponding to a station No. disconnects the specified slave station from the master station.
1...Connected
0...Unconnected
OFF
ON
5sec
5sec
bit15
bit14
..........
bit2
bit1
bit0
Station
No. 15
Station
No. 14
..........
Station
No. 2
Station
No. 1
Station
No. 0
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......