5.4 PLC Side Setting
5 - 79
5
E
T
H
E
RNET CONNEC
T
ION
(2) Exchange condition setting switch
*1
: Necessary : As necessary : Not necessary
*1
The exchange condition setting switches of A1SJ71E71-B5-S3 and A1SJ71E71-B2-S3 are specified as the below.
: Necessary : As necessary : Not necessary
POINT
POINT
POINT
When the switch setting has been changed
Turn the PLC CPU OFF then ON again, or reset the PLC CPU.
■3.
Sequence program
The sequence program for initial processing and communication line opening processing are required.
(1) Programming condition
This program performs the initial processing of the Ethernet module and the opening processing of connection No. 1
when the stopping PLC CPU starts running.
(a)
I/O signal of Ethernet module
➠
For A Ethernet Interface Module User’s Manual
(b)
Device used by user
Exchange condition setting
switch
Setting
switch
Description
Set value
Setting necessity at GOT
connection
SW1
Selection of line processing at TCP
timeout error
OFF
SW2
Data code setting
(binary code)
OFF
(fixed)
SW3
(Must not to be used)
OFF
(fixed)
SW4
SW5
SW6
SW7
CPU exchange timing setting
(Enable write at RUN time)
ON
(fixed)
SW8
Initial timing setting
OFF
Exchange condition
setting switch
Setting
switch
Description
Set value
Setting necessity at
GOT connection
SW1
Selection of line processing at
TCP timeout error
OFF
SW2
Data code setting
(binary code)
OFF
(fixed)
SW3
CPU exchange timing setting
(Enable write at RUN time)
ON
(fixed)
SW4
Initial timing setting
OFF
Device
Application
M102
COM.ERR turned off command
D100
IP address of Ethernet module
D110
Application setting
D111
Port No. of Ethernet module
D112 to D113
IP address of GOT
D114
Port No. of GOT
D200
Initial fault code
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
OFF
ON
SW1
SW2
SW3
SW4
OFF
ON
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......