14 - 32
14.2 System Configuration
■4.
Connecting FREQROL-A500, A500L series
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating each parameter.
(1) Communication port and corresponding parameters
(2) Communication settings of inverter
Set the following parameters using the PU (parameter unit). Do not change these parameters, even though they can
be monitored from the GOT. If they are changed, communication with the GOT is disabled.
*1
Setting items are parameter names described in the manual of FREQROL-A500 and A500L series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
*3
Inverter default values (No need to change)
*4
Since the value has been set as a default, no setting is required when connecting to the PU connector on the inverter side.
*5
There is no Protocol selection setting on the inverter side.
*6
The setting is required on the inverter side when FR-A5NR is used.
GOT connection destination
Parameters corresponding to inverter
PU connector
Pr.79, Pr.117 to Pr.124, Pr.342
FR-A5NR (Option unit)
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342
Setting item
*1
Parameter No.
Set value
Contents of setting
PU connector
FR-A5NR
Communication station number
Pr.117
Pr.331
0 to 31
➠
Communication speed
*2
Pr.118
Pr.332
192
*4
19200bps
Stop bit length
*2
Pr.119
Pr.333
10
Data length: 7bit
Stop bit length: 1bit
Parity check presence/absence
*2
Pr.120
Pr.334
1
Odd
Number of communication retries
Pr.121
Pr.335
9999
The inverter will not come to an
alarm stop.
Communication check time interval
Pr.122
Pr.336
9999
Communication check
suspension
Wait time setting
Pr.123
Pr.337
0
0ms
CRLF presence/ absence selection
Pr.124
Pr.341
1
*3
With CR, without LF
Protocol selection
*5
-
-
-
-
Operation mode selection
Pr.79
PU
connector
1
PU operation mode
FR-A5NR
0
*3
External operation mode at power
on
Link start mode selection
*6
-
Pr.340
1
Computer link operation
E2PROM write selection
Pr.342
0
*3
Written to RAM and EEPROM
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......