5 - 40
5.4 PLC Side Setting
5.4.3
Connecting to Ethernet module (MELSEC iQ-R Series)
This section describes the settings of the GOT and Ethernet module (MELSEC iQ-R Series) in the following case of the
system configuration.
POINT
POINT
POINT
Ethernet module (MELSEC iQ-R Series)
For details of the Ethernet module (MELSEC iQ-R Series), refer to the following manual.
➠
Manuals of MELSEC iQ-R Series
■1.
System configuration
*1
The Ethernet module is mounted on the base unit slot 0.
The Start XY No. of the Ethernet module is set to "0".
■2.
[Module parameter] of GX Works3
(1) Module parameter of Ethernet module (MELSEC iQ-R Series)
*1
*1
Set [Module parameter] of the port under [Module information].
Item
Set value
Setting necessity at GOT
connection
IP Address
192.168.3.19
Subnet Mask
-
Default Gateway
-
Setting Method of Network No. and Station No.
Do Not Use IP Address
Network No.
*2
1
Station No.
*3
2
<GOT>
(Use the default value for settings
other than the following.)
*1
Network No.
:1
PLC No.
:1
IP address
:192.168.3.18
Port No.
:5001
Communication format :UDP (fixed)
Network No.
:1
PLC No.
:2
IP address
:192.168.3.19
Port No.
:5001
Communication format :UDP (fixed)
<Ethernet module>
(Use the default value for settings
other than the following.)
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......