4.3 MELSEC Redundant Setting
4 - 89
4
HOW T
O
MONIT
O
R REDUNT
ANT SYSTEM
4.3
MELSEC Redundant Setting
The following explains the setting for automatically change the monitoring target of the GOT when monitoring a RCPU
redundant system, QCPU redundant system.
POINT
POINT
POINT
Before making the MELSEC redundant setting
In the MELSEC redundant setting, do not set stations other than redundant CPUs.
Step 1.
Select [Common]
[Controller Setting]
[MELSEC Redundant] from the menu.
Step 2.
The setting dialog box appears. Make the settings with reference to the following explanation.
Step 3.
Make the settings for the MELSEC redundant setting.
In the MELSEC Redundant Setting dialog box, settings can be made for each channel of the controller.
*1
For details of *1, refer to the explanation below.
(Example: Ethernet connection (Station No. 5), redundant CPU pair No. 1 and No. 2, redundant CPU station No. 1 to 4)
Item
Contents
Model
CH1 to CH4
Select a tab of the CH No. for the MELSEC redundant setting.
Follow the redundant
system via a serial
interface
Select this item to monitor the control system as a host station at serial connection.
Pair No.
*1
NW No.
Set the network No. (1 to 225) for each of pair numbers (1 to 64).
Upper row: Setting for the first redundant CPU.
Lower row: Setting for the second redundant CPU.
(The same value as the value set for the first redundant CPU is displayed)
Station
No.
Set the station No. (1 to 63) of the redundant CPU for each of pair numbers (1 to 64).
Upper row: Setting for the first redundant CPU.
Lower row: Setting for the second redundant CPU.
(The value of "Setting for the first redundant CPU" + 1 is displayed)
New
Create a new pair No.
Duplicate
Copies one setting of the selected pair number to append it at the last line.
Delete
Deletes one setting of the selected pair.
After deletion, the succeeding pair numbers are renumbered to fill the deleted pair number.
Delete All
Deletes the setting of all pair numbers.
Copy All
Copies the MELSEC redundant setting on the selected CH No. tab.
Paste All
Pastes the copied MELSEC redundant setting in the selected CH No. tab.
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......