5 - 52
5.4 PLC Side Setting
5.4.6
Connecting to MELSEC-Q/L Series built-in Ethernet port CPU (one-to-
one connection)
This section describes the settings of the GOT and Built-in Ethernet port CPU in the following case of system configuration.
POINT
POINT
POINT
Connecting to Built-in Ethernet port CPU
For details of Built-in Ethernet port CPU, refer to the following manual.
➠
QnUCPU User's Manual (Communication via Built-in Ethernet Port)
➠
MELSEC-L CPU Module User's Manual (Built-In Ethernet Function)
■1.
System configuration
(When the PLC side [MELSOFT Connection Extended Setting] is the default value)
For connecting one Built-in Ethernet port QCPU to one GOT, the PLC side settings are not required. Set [Ethernet] for
[Controller Setting] on GT Designer3, and then connect Built-in Ethernet port QCPU to the GOT.
*1
For the settings when using system devices including a hub and a transceiver, refer to the following.
➠
5.4.7 Connecting to MELSEC-Q/L Series built-in Ethernet port CPU (multiple connection)
*2
These setting items do not exist at the PLC side. However, the virtual values must be set on the GOT side.
➠
(2) [Controller Setting] and [Ethernet] of GT Designer3
(1) [PLC parameter] of GX Works2
Use the GX Works2 Version1.535H or later.
(a)
Built-in Ethernet
Item
Set value
Setting necessity at GOT connection
IP address
192.168.3.39
(Use default value)
○
Subnet mask pattern
-
×
<GOT>
(The settings other than the
following are set to the default)
*1
*2
*2
Network No.
: 1
PLC No.
: 1
IP address
: 192.168.3.18
Port No.
: 5001
Communication
format
: UDP (fixed)
Network No.
: 1 (virtual)
PLC No.
: 2 (virtual)
IP address
: 192.168.3.39
Communication
format
: UDP
<Connecting to Built-in Ethernet port CPU>
(The following settings are set to the default)
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......