8.4 Precautions
8 - 39
8
BU
S CON
NECTION
8.4
Precautions
8.4.1
GT15-C [ ] EXSS-1, GT15-C [ ] BS
■1.
Composition of GT15-C EXSS-1
It is composed of GT15-EXCNB (0.5m) and GT15-C BS (10 to 30m).
Calculate the cable length based on GT15-C100EXSS-1(10m), GT15-C200EXSS-1(20m) and GT15-C300EXSS-
1(30m).
■2.
GT15-C EXSS-1 connector
Connect the connectors as follows:
GT15-EXCNB
PLC CPU side
GT15-C BS
GOT
side
■3.
Grounding
(1) When using GT15-C EXSS-1
Step 1.
Connect the LG and FG terminals of the terminal block on the GOT unit power and ground them with a
cable.
Step 2.
Use the GT15-C BS's FG cable of 28cm or less.
Step 3.
Do not connect the GT15-EXCNB's FG ground cable.
Step 4.
Connect the GT15-C BS's FG cable on the GOT side to FG of the GOT unit power's terminal block.
Step 5.
Connect the GT15-C BS's FG cable on the PLC side to FG of the PLC's power supply module.
Step 6.
Connect the LG and FG terminals of the terminal block on the PLC and ground them with a cable.
(2) When using GT15-C BS
Follow the GOT side grounding steps in (a) above for both GOTs.
(GT15-EXCNB)
(GT15-C□BS)
PLC side
GOT side
FG
LG
N
L
PLC
Not connected
(GT15-EXCNB)
GOT
OUT
IN
FG
LG
N
L
2SQ cables to
FG terminals,
28cm or less
2SQ cables to
FG terminals,
28cm or less
(GT15-C□BS)
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......