1.1 Setting the Communication Interface
1 - 13
1
PREP
ARA
T
O
R
Y PROC
EDURE
S FOR MONIT
O
RING
1.1.2
GOT Ethernet Setting
The GOT can be connected to a different network by using the following network.
1) GOT IP Address Setting
Set the following communication port setting.
Standard port (When using GT25-W, port 1)
Set [GOT IP Address] and [Subnet Mask] in the standard port with a bult-in GOT, or port 1.
Extension port (When using GT25-W, port 2)
Set [GOT IP Address] and [Subnet Mask] in the extension port (the Ethernet interface for the Ethernet
communication module), or port 2 with a bult-in GOT.
When using the GOT other than GT25-W, BootOS Version Z or later is required to use the extension port.
For details on writing the BootOS, refer to the following manual.
➠
GT Designer3 (GOT2000) Screen Design Manual
Wireless LAN
Set [GOT IP Address], [Subnet Mask], [Peripheral S/W Communication Port No.], and [Transparent Port No.]
for the wireless LAN interface.
2) GOT Ethernet Common Setting
Set the following setting which is common to the standard port and the extension port, or port 1 and port 2.
• [Default Gateway]
• [Peripheral S/W Communication Port No.]
• [Transparent Port No.]
3) IP Filter Setting
By configuring the IP filter setting, the access from the specific IP address can be permitted or shut off.
■1.
GOT IP Address Setting
Set the GOT IP address.
(1) [Standard Port] or [Port 1]
The following shows an example for [Standard Port].
Step 1.
Select [System]
→
[GOT Setup]
→
[GOT Ethernet Setting]
→
[GOT IP Address Setting]
→
[Standard
Port] from the menu.
Step 2.
Set the followings.
Item
Description
Range
Update GOT Ethernet standard
port setting
The GOT Ethernet standard port settings are applied on GOT.
-
GOT IP Address
Set the IP address of the GOT IP Address.
(Default:192.168.3.18)
0.0.0.0 to 255.255.255.255
Subnet Mask
Set the subnet mask for the sub network. (Only for connection via router)
If the sub network is not used, the default value is set.
(Default: 255.255.255.0)
0.0.0.0 to 255.255.255.255
Select from GOT Setting List.
Select the GOT set in [GOT Setting List] dialog.
➠
GT Designer3 (GOT2000) Screen Design Manual
-
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......