14.2 System Configuration
14 - 37
INVERTER
C
O
NNE
CTION
14
■9.
Connecting FREQROL-F700PJ series
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating each parameter.
(1) Communication port and corresponding parameters
(2) Communication settings of inverter
Set the following parameters using the PU (parameter unit). Before setting the parameters, set Pr.160 (Extended
function display selection) to 0 so that simple mode + extended mode parameters are displayed.
Do not change these parameters, even though they can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
*1
Setting items are parameter names described in the manual of FREQROL-F700 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
*3
Inverter default values (No need to change)
POINT
POINT
POINT
Automatic setting with Pr.999
If Pr.999 is set as the following, the communication settings other than [PU communication
station number] and [Communication EEPROM write selection] can be automatically set in a
batch to the default communication settings of the GOT side.
*1
When monitoring the value of Pr.999, 9999 is always monitored.
GOT connection destination
Parameters corresponding to inverter
PU connector
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.342, Pr.549
Setting item
*1
Parameter No.
Set value
Contents of setting
PU communication station number
Pr.117
0 to 31
➠
PU communication speed
*2
Pr.118
192
*3
19200bps
PU communication stop bit length
Pr.119
10
Data length: 7bit
Stop bit length: 1bit
PU communication parity check
*2
Pr.120
1
Odd
Number of PU communication retries
Pr.121
9999
The inverter will not come to an
alarm stop.
PU communication check time interval
Pr.122
9999
Communication check suspension
PU communication waiting time setting
Pr.123
0
0ms
PU communication CR/LF selection
Pr.124
1
*3
With CR, without LF
Protocol selection
Pr.549
0
*3
Mitsubishi Electric inverter protocol
Operation mode selection
Pr.79
0
*3
External operation mode at power
on
Communication startup mode selection
Pr.340
1
Network operation mode.
Communication EEPROM write selection
Pr.342
0
*3
Written to RAM and EEPROM
Parameter No.
Set value
Description
Operation in parameter setting mode
Pr.999
*1
10
GOT Initial settings (PU connector)
[AUTO] [GOT] [1]Write
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......