12 - 68
12.4 PLC Side Setting
(2) Program condition (for FROM/TO instruction)
This program writes parameters to the buffer memory when PLC CPU status changes from STOP to RUN and
automatically starts the data link with FROM/TO instruction.
(a)
I/O signal of CC-Link module
➠
Control & Communication Link System Master/Local Module Type AJ61BT11/A1SJ61BT11
User's Manual
(b)
Devices used by user
(c)
Buffer memory settings used in the present example
*1
Details for the station data are shown below.
For 1) and 2), set the same station No. and number of station occupied settings as those of the GOT.
For 3), the setting is fixed.
Device
Application
M100, M101
Flag for parameter setting
M102, M103
Flag for data link startup
D0
Number of connected modules
D1
Number of retry
D2
Automatic reconnection station count
D3
Operation specification in the case of CPU failure
D4
Reserved station specification (Station No. 1 to Station No. 16)
D5
Error invalid station specification (Station No. 1 to Station No. 16)
D6
Station data (first module)
D400
Error code in the case of data link startup failure
Buffer memory
address
Item
Set value
Decimal (Hex)
1 (1H)
Number of connected modules
1 (1 module)
2 (2H)
Number of retry
3 (3times)
3 (3H)
Automatic reconnection station count
1 (1 station)
6 (6H)
Operation specification in the case of CPU failure
0 (stop)
16 (10H)
Reserved station specification (Station No. 1 to Station No. 16)
0 (No specification)
20 (14H)
Error invalid station specification
(Station No. 1 to Station No. 16)
0 (No specification)
32 (20H)
Station data (first module)
*1
2101H
1) Station No. (Set the same station No. as that of the GOT.)
01H to 40H: Station No. 1 to Station No. 64
2) Number of stations occupied (Set the same setting of the number of station occupied as that of the GOT.)
1H: Exclusive station 1
2H: Exclusive station 2
3H: Exclusive station 3
4H: Exclusive station 4
3) Station type (2H: Set it to intelligent device station.)
0H: Remote I/O station
1H: Remote device station
2H: Intelligent device station (Incl. local station)
b15
b12
to
b11
b8
to
b7
to
b0
3)
2)
1)
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......