14 - 36
14.2 System Configuration
■8.
Connecting FREQROL-F700/700P series
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating each parameter.
(1) Communication port and corresponding parameters
(2) Communication settings of inverter
Set the following parameters using the PU (parameter unit). Before setting the parameters, set Pr.160 (User group
read selection) to 0 so that simple mode + extended mode parameters are displayed.
Do not change these parameters, even though they can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
*1
Setting items are parameter names described in the manual of FREQROL-F700 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
*3
Inverter default values (No need to change)
*4
Since the value has been set as a default, no setting is required when connecting to the PU connector on the inverter side.
POINT
POINT
POINT
Automatic setting with Pr.999 (FREQROL-F700P series only)
If Pr.999 is set as the following, the communication settings other than [PU communication
station number] and [Communication EEPROM write selection] can be automatically set in a
batch to the default communication settings of the GOT side.
*1
When monitoring the value of Pr.999, 9999 is always monitored.
GOT connection destination
Parameters corresponding to inverter
PU connector
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.342
RS-485 terminal
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342, Pr.549
Setting item
*1
Parameter No.
Set value
Contents of setting
PU connector
RS-485
PU communication station number/RS-485
communication station number
Pr.117
Pr.331
0 to 31
➠
PU communication speed/RS-485
communication speed
*2
Pr.118
Pr.332
192
*4
19200bps
PU communication stop bit length/
RS-485 communication stop bit length
*2
Pr.119
Pr.333
10
Data length: 7bit
Stop bit length: 1bit
PU communication parity check/
RS-485 communication parity check
*2
Pr.120
Pr.334
1
Odd
Number of PU communication retries/
RS-485 communication retry count
Pr.121
Pr.335
9999
The inverter will not come to an
alarm stop.
PU communication check time interval/
RS-485 communication check time interval
Pr.122
Pr.336
9999
*4
Communication check suspension
PU communication waiting time setting/
RS-485 communication waiting time setting
Pr.123
Pr.337
0
0ms
PU communication CR/LF selection/
RS-485 communication CR/LF selection
Pr.124
Pr.341
1
*3
With CR, without LF
Protocol selection
-
Pr.549
0
*3
Mitsubishi Electric inverter protocol
Operation mode selection
Pr.79
PU
connector
1
PU operation mode
RS-485
0
*3
External operation mode at power
on
Communication startup mode selection
Pr.340
PU
connector
0
*3
Refer to Pr.79 settings.
RS-485
1
Network operation mode.
Communication EEPROM write selection
Pr.342
0
*3
Written to RAM and EEPROM
Parameter No.
Set value
Description
Operation in parameter setting mode
Pr.999
*1
10
GOT Initial settings (PU connector)
[AUTO]
→
[GOT]
→
[1]Write
11
GOTInitial settings (RS-485 terminal)
-
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......