Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-54-
Function
code
Name
Description
Default
coefficient of
vector control
Current-loop
proportional
coefficient P
0
–65535
1000
Current-loop
integral
coefficient I
0
–65535
1000
Torque setting
method
1: Keypad (P03.12)
2: AI1
3: AI2
4: AI3
5: Pulse frequency HDIA
6: Multi-step torque
7: Modbus/Modbus TCP communication
8: PROFIBUS/CANopen/DeviceNet communication
9: Ethernet communication
10: Pulse frequency HDIB
11: EtherCAT/PROFINET/EtherNet IP communication
12: Programmable card
Note:
For these settings, 100% corresponds to the
motor rated current.
1
Torque set
through
keypad
-300.0%
–300.0% (of the motor rated current)
50.0%
Torque
reference filter
time
0.000
–10.000s
0.010s
Setting source
of forward
rotation
upper-limit
frequency in
torque control
0: Keypad (P03.16)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
5: Multi-step setting
6: Modbus/Modbus TCP communication
7: PROFIBUS/CANopen/DeviceNet communication
8: Ethernet communication
0