Goodrive350A series high-performance multifunction VFD
Function parameter list
-218-
Function
code
Name
Description
Default
Modify
P12.16
Rated frequency of
SM 2
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
◎
P12.17
Number of pole
pairs of SM 2
1
–128
2
◎
P12.18
Rated voltage of
SM 2
0
–1200V
Model
depended
◎
P12.19
Rated current of SM
2
0.8
–6000.0A
Model
depended
◎
P12.20
Stator resistance of
SM 2
0.001
–65.535Ω
Model
depended
○
P12.21
Direct-axis
inductance of SM 2
0.01
–655.35mH
Model
depended
○
P12.22
Quadrature-axis
inductance of SM 2
0.01
–655.35mH
Model
depended
○
P12.23
Counter-emf
constant of SM 2
0
–10000V
300
○
P12.24
Reserved
P12.25
Reserved
P12.26
Overload protection
selection of motor 2
0: No protection
1: Common motor protection (with low-speed
compensation).
2: Variable-frequency motor protection
(without low speed compensation).
2
◎
P12.27
Overload protection
coefficient of motor
2
Motor overload multiples M=Iout/(In*K)
In is rated motor current, lout is VFD output
current, and K is motor overload protection
coefficient.
A smaller value of K indicates a bigger value
of M.
When M=116%, protection is performed after
motor overload lasts for 1 hour; when
M=150%, protection is performed after motor
overload lasts for 12 minutes; when M=180%,
protection is performed after motor overload
lasts for 5 minutes; when M=200%, protection
is performed after motor overload lasts for 60
seconds; and when M≥400%, protection is
100.0%
○