Goodrive350A series high-performance multifunction VFD
Function parameter list
-165-
Function
code
Name
Description
Default
Modify
P04.15
Torque boost cut-off
of motor 2
Setting range of P04.14: 0.0%: (automatic);
0.1%
–10.0%
Setting range of P04.15: 0.0%
–50.0% (of the
rated frequency of motor 2)
20.0%
○
P04.16
V/F frequency point
1 of motor 2
Note: Refer to the descriptions for
Setting range of P04.16: 0.00Hz
Setting range of P04.17: 0.0%
–110.0% (of the
rated voltage of motor 2)
Setting range of P04.18: P04.16
Setting range of P04.19: 0.0%
–110.0% (of the
rated voltage of motor 2)
Setting range of P04.20: P04.18
(rated frequency of AM 2) or P04.18
(rated frequency of SM 2)
Setting range of P04.21: 0.0%
–110.0% (of the
rated voltage of motor 2)
0.00Hz
○
P04.17
V/F voltage point 1
of motor 2
0.0%
○
P04.18
V/F frequency point
2 of motor 2
0.00Hz
○
P04.19
V/F voltage point 2
of motor 2
00.0%
○
P04.20
V/F frequency point
3 of motor 2
0.00Hz
○
P04.21
V/F voltage point 3
of motor 2
0.0%
○
P04.22
V/F slip
compensation gain
of motor 2
Used to compensate for the motor rotating
speed change caused by load change in the
space voltage vector mode, and thus improve
the rigidity of the mechanical characteristics
of the motor. You need to calculate the rated
slip frequency of the motor as follows:
△
f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the
motor, corresponding to function code
P12.02. n is the rated rotating speed of the
motor, corresponding to function code
P12.03. p is the number of pole pairs of the
motor. 100.0% corresponds to the rated slip
frequency
△
f of motor 2.
Setting range: 0.0
–200.0%
0.0%
○
P04.23
Low-frequency
oscillation control
factor of motor 2
In space voltage vector control mode, the
motor, especially the large-power motor, may
experience current oscillation at certain
frequencies, which may cause unstable motor
running, or even VFD overcurrent. You can
adjust the two function codes properly to
10
○
P04.24
High-frequency
oscillation control
factor of motor 2
10
○