Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-106-
Set
value
Function
Description
communication
to 1, output OFF signal when it is set to 0.
26
DC bus voltage established
Output is valid when the bus voltage is above the
undervoltage threshold of the inverter
27
Z pulse output
Output is valid when the encoder Z pulse is
arrived, and is invalid after 10 ms.
28
During pulse superposition
Output is valid when the pulse superposition
terminal input function is valid
29
STO action
Output when STO fault occurred
30
Positioning completed
Output is valid when position control positioning is
completed
31
Spindle zeroing completed
Output is valid when spindle zeroing is completed
32
Spindle scale-division completed
Output is valid when spindle scale-division is
completed
33
In speed limit
Output is valid when the frequency is limited
34
Virtual terminal output of
EtherCAT/PROFINET/
EtherNet IP communication
The corresponding signal is output according to
the set value of PROFINET communication. When
it is set to 1, the ON signal is output, and when it is
set to 0, the OFF signal is output.
35
Reserved
36
Speed/position control switchover
completed
Output is valid when the mode switchover is
completed
37
Any frequency reached
The frequency reached signal is output when the
present ramp reference frequency is greater than
the detection value for frequency being reached.
38
–40
Reserved
41
Y1
Y1 from the programmable card
42
Y2
Y2 from the programmable card