Goodrive350A series high-performance multifunction VFD
Function parameter list
-193-
Function
code
Name
Description
Default
Modify
P08.18
Fall time of
wobbling frequency
0.1
–3600.0s
5.0s
○
P08.19
Switching frequency
of ACC/DEC time
0.00
–P00.03 (Max. output frequency)
0.00Hz: No switchover
If the running frequency is greater than
P08.19, switch to ACC/DEC time 2.
0.00Hz
○
P08.20
Frequency
threshold of the
start of droop
control
0.00
–50.00Hz
2.00Hz
○
P08.21
Reference
frequency of
ACC/DEC time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note:
Valid only for straight-line ACC/DEC
0
◎
P08.22
Output torque
calculation method
0: Based on torque current
1: Based on output power
0
○
P08.23
Number of decimal
points of frequency
0: Two
1: One
0
○
P08.24
Number of decimal
places of linear
speed
0: No decimal place
1: One
2: Two
3: Three
0
○
P08.25
Set counting value P08.26
–65535
0
○
P08.26
Designated
counting value
0
0
○
P08.27
Set running time
0
–65535min
0min
○
P08.28
Auto fault reset
count
Auto fault reset count: When the VFD uses
automatic fault reset, it is used to set the
number of automatic fault reset times. When
the number of continuous reset times
exceeds the value, the VFD reports a fault
and stops.
Auto fault reset interval: Time interval from
when a fault occurred to when automatic fault
reset takes effect.
After VFD starts, If no fault occurred within
600s after the VFD starts, the number of
0
○
P08.29
Auto fault reset
interval
1.0s
○