Goodrive350A series high-performance multifunction VFD
Function parameter list
-199-
Function
code
Name
Description
Default
Modify
1: No lock on STO alarm
No lock on STO alarm indicates STO alarm
disappears automatically after state
restoration if STO occurs.
P08.53
Upper limit
frequency bias
value in torque
control
0.00 Hz
–P00.03 (Max. output frequency)
Note:
Valid only for torque control.
0.00Hz
○
P08.54
Upper limit
frequency
ACC/DEC selection
in torque control
0: No limit on acceleration or deceleration
1: ACC/DEC time 1
2: ACC/DEC time 2
3: ACC/DEC time 3
4: ACC/DEC time 4
0
○
P08.55
Enabling auto
carrier frequency
reduction
0: Disable
1: Enable
Note:
Automatic carrier frequency reduction
indicates that the VFD automatically reduces
the carrier frequency when detecting the heat
sink temperature exceeds the rated
temperature. When the temperature
decreases to a certain degree, the carrier
frequency recovers. This function reduces the
chance of VFD overheat alarm.
0
○
P08.56
Min. carrier
frequency
0.0
–15.0kHz
Depends
on model
●
P08.57
Temperature point
of auto carrier
frequency reduction
40.0
–85.0°C
70.0°C
○
P08.58
Interval of carrier
frequency reduction
0
–30min
10min
○
P08.59
AI1 disconnection
detection threshold
0
–100%
0
○
P08.60
AI2 disconnection
detection threshold
0
–100%
0
○
P08.61
AI3 disconnection
detection threshold
0
–100%
0
○
P08.62 Output current filter 0.000
–10.000s
0.000s
○