Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-81-
Function
code
Name
Description
Default
21: ACC/DEC time selection 1
22: ACC/DEC time selection 2
30: Disable ACC/DEC
ACC time 2
0.0
–3600.0s
Model
depended
DEC time 2
0.0
–3600.0s
Model
depended
ACC time 3
0.0
–3600.0s
Model
depended
DEC time 3
0.0
–3600.0s
Model
depended
ACC time 4
0.0
–3600.0s
Model
depended
DEC time 4
0.0
–3600.0s
Model
depended
Running frequency of jog 0.00Hz
–P00.03 (Max. output frequency)
5.00Hz
ACC time for jog
0.0
–3600.0s
Model
depended
DEC time for jog
0.0
–3600.0s
Model
depended
Switching frequency of
ACC/DEC time
0.00
–P00.03(Max. output frequency)
0.00Hz: No switchover
If the running frequency is greater than
P08.19, switch to ACC/DEC time 2.
0
Reference frequency of
ACC/DEC time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note:
Valid only for straight-line
ACC/DEC
0
Auto fault reset count
0
–10
0
Auto fault reset interval
0.1
–3600.0s
1.0s
5.5.8 Frequency setting
The VFD supports multiple frequency setting methods, which can be divided into two types: main
reference channel and auxiliary reference channel.
There are two main reference channels, namely frequency reference channel A and frequency
reference channel B. These two channels support simple arithmetical operation between each other,
and they can be switched dynamically by setting multi-function terminals.