Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-118-
Function
code
Name
Description
Default
12: Reserved
PID digital setting
-100.0%
–100.0%
0.0%
PID feedback
source
0: AI1
1: AI2
2: AI3
3: High-speed pulse HDIA
4: Modbus/Modbus TCP communication
5: PROFIBUS/CANopen/DevicneNET
communication
6: Ethernet communication
7: High-speed pulse HDIB
8: EtherCAT/PROFINET/EtherNet IP
communication
9: Programmable card
10: Reserved
0
PID output
characteristics
selection
0: PID output is positive characteristic
1: PID output is negative characteristic
0
Proportional gain
(Kp)
0.00
–100.00
1.80
Integral time (Ti)
0.01
–10.00s
0.90s
Differential time (Td) 0.00–10.00s
0.00s
Sampling period (T) 0.000–10.000s
0.100s
PID control
deviation limit
0.0
–100.0%
0.0%
PID output upper
limit
–100.0% (max. frequency or voltage)
100.0%
PID output lower
limit
-100.0%
–P09.09 (max. frequency or voltage)
0.0%
Feedback offline
detection value
0.0
–100.0%
0.0%
Feedback offline
detection time
0.0
–3600.0s
1.0s
PID control
selection
0x0000
–0x1111
Ones place:
0: Continue integral control after the frequency
0x0001