Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-105-
Set
value
Function
Description
9
Running in zero speed
Output ON signal when the VFD output frequency
and reference frequency are both zero.
10
Reach upper limit frequency
Output ON signal when the running frequency
reaches upper limit frequency
11
Reach lower limit frequency
Output ON signal when the running frequency
reached lower limit frequency
12
Ready to run
Main circuit and control circuit powers are
established, the protection functions do not act;
when the VFD is ready to run, output ON signal.
13
In pre-exciting
Output ON signal during pre-exciting of the VFD
14
Overload pre-alarm
Output ON signal after the pre-alarm time elapsed
based on the pre-alarm threshold; see
P11.08
–P11.10 for details.
15
Underload pre-alarm
Output ON signal after the pre-alarm time elapsed
based on the pre-alarm threshold; see
P11.11
–P11.12 for details.
16
Simple PLC state completed
Output signal when current stage of simple PLC is
completed
17
Simple PLC cycle completed
Output signal when a single cycle of simple PLC
operation is completed
23
Virtual terminal output of
Modbus/Modbus TCP
communication
Output corresponding signal based on the set
value of Modbus/Modbus TCP; output ON signal
when it is set to 1, output OFF signal when it is set
to 0
24
Virtual terminal output of
POROFIBUS/CANopen/DeviceNet
communication
Output corresponding signal based on the set
value of POROFIBUS/CANopen/DeviceNet;
output ON signal when it is set to 1, output OFF
signal when it is set to 0
25
Virtual terminal output of Ethernet
Output corresponding signal based on the set
value of Ethernet; output ON signal when it is set