Goodrive350A series high-performance multifunction VFD
Function parameter list
-170-
Function
code
Name
Description
Default
Modify
Tens place: HDIB input type
0: HDIB is high-speed pulse input
1: HDIB is digital input
P05.01
Function of S1
terminal
0: No function
1: Forward running
2: Reverse running
3: 3-wire control/Sin
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Running pause
9: External fault input
10: Frequency increase (UP)
11: Frequency decrease (DOWN)
12: Clear frequency increase/decrease
setting
13: Switchover between setup A and setup B
14: Switchover between combination setup
and setup A
15: Switchover between combination setup
and setup B
16: Multi-step speed terminal 1
17: Multi-step speed terminal 2
18: Multi-step speed terminal 3
19: Multi-step speed terminal 4
20: Multi-step speed pause
21: Acceleration/deceleration time selection 1
22: Acceleration/deceleration time selection 2
23: Simple PLC stop reset
24: Simple PLC pause
25: PID control pause
26: Wobbling frequency pause
27: Wobbling frequency reset
28: Counter reset
29: Switchover between speed control and
torque control
1
◎
P05.02
Function of S2
terminal
4
◎
P05.03
Function of S3
terminal
7
◎
P05.04
Function of S4
terminal
0
◎
P05.05
Function of HDIA
terminal
0
◎
P05.06
Function of HDIB
terminal
0
◎