Goodrive350A series high-performance multifunction VFD
Function parameter list
-168-
Function
code
Name
Description
Default
Modify
closed-loop
proportional
coefficient in SM
V/F control
the function code is used to set the
proportional coefficient of reactive current
closed-loop control.
Setting range: 0
–3000
P04.38
Reactive current
closed-loop integral
time in SM V/F
control
When the SM V/F control mode is enabled,
the function code is used to set the integral
coefficient of reactive current closed-loop
control.
Setting range: 0
–3000
30
○
P04.39
Reactive current
closed-loop output
limit in SM V/F
control
When the SM V/F control mode is enabled,
the function code is used to set the output
limit of the reactive current closed-loop
control. A greater value indicates a higher
reactive closed-loop compensation voltage
and higher output power of the motor. In
general, you do not need to modify the
function code.
Setting range: 0
–16000
8000
○
P04.40
Enabling IF mode
for AM 1
0: Disable
1: Enable
0
◎
P04.41
Current setting in IF
mode for AM 1
When IF control is adopted for AM 1, the
function code is used to set the output
current. The value is a percentage in relative
to the rated current of the motor.
Setting range: 0.0
–200.0%
120.0%
○
P04.42
Proportional
coefficient in IF
mode for AM 1
When IF control is adopted for AM 1, the
function code is used to set the proportional
coefficient of the output current closed-loop
control.
Setting range: 0
–5000
650
○
P04.43
Integral coefficient
in IF mode for AM 1
When IF control is adopted for AM 1, the
function code is used to set the integral
coefficient of the output current closed-loop
control.
Setting range: 0
–5000
350
○
P04.44
Frequency
threshold for
0.00Hz
–P04.50
10.00Hz
○