Goodrive350A series high-performance multifunction VFD
Function parameter list
-276-
Function
code
Name
Description
Default
value
Modify
P28.21
EC PT1000
calibration upper
limit digital
0
–4096
3100
○
P28.22
EC PT1000
calibration lower
limit digital
0
–4096
1100
○
P28.23
Detecting for
PT100/PT1000
disconnection from
EC
0x00
–0x11
Ones place: PT100 disconnection detection
0: Disable
1: Enable
Tens place: PT1000 disconnection detection
0: Disable
1: Enable
0x00
◎
P28.24
Enabling digital
calibration in EC
PT100/PT1000
temperature
detection
0
–4
0: Disable
1: Enable PT100 lower limit digital calibration.
2: Enable PT100 upper limit digital calibration.
3: Enable PT1000 lower limit digital
calibration.
4: Enable PT1000 upper limit digital
calibration.
0
○
P28.25
Type of sensor for
AI/AO card to
detect motor
temperature
0
–4
0: No temperature sensor
1: PT100
2: PT1000
3: KTY84
4: PTC (Measuring resistance only)
Note:
Temperature is displayed through
P19.11. To measure temperature, switch the
output of AO1 to current, and connect one end
of the temperature resistor to AI1 and AO1,
and the other end to GND.
0
◎
P28.26
AI/AO detected
motor OH
protection threshold
0.0
–200.0°C
Note:
When the motor temperature exceeds
the threshold, the VFD releases the OT alarm.
110.0°C
○