Goodrive350A series high-performance multifunction VFD
Function parameter list
-254-
Function
code
Name
Description
Default
value
Modify
positioning arrival positioning position is reached.
Setting range: 0.000
–60.000s
P21.23
Home search
speed
0.00
–50.00Hz
2.00Hz
○
P21.24
Home position
offset
0
–65535
0
○
P21.25
Hold time of
positioning
completion signal
The hold time of positioning completion
signal, the function code is also valid for
positioning completion signal of spindle
orientation.
Setting range: 0.000
–60.000s
0.200s
○
P21.26
value
P21.26: -9999
–32767
–3000.0/ms
The function is valid only when P00.06=12 or
1: Input terminal function 68
When the terminal rise edge is detected, the
pulse setting is increased by P21.26, and the
pulse given channel is compensated at the
rate specified by P21.27.
2: Input terminal function 67
When the terminal is valid, the pulse value is
superposed to the pulse given channel at the
rate specified by P21.27.
Note:
P05.09 may have slight impact on the
actual superposition value.
Example:
P21.27 = 1.0/ms
P05.05 = 67
When the S5 terminal input signal is 0.5s, the
actual number of pulses superposed is 500.
3: Input terminal function 69
The timing sequence of this value is the same
as that of the previous value, with the only
difference that the number is negative.
Note:
The pulses are superposed to the pulse
given channels (A2 and B2), and the functions
such as the filter and electric cam for pulses
0
○
P21.27
Pulse superposition
speed
8.0/ms
○
P21.28
ACC/DEC time after
pulse disabling
5.0s
○