Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-104-
5.5.12 Digital output
The VFD provides two groups of relay output terminals, one open collector Y output terminal and one
high-speed pulse output (HDO) terminal. All the digital output terminal functions can be programmed
by function codes, of which the high-speed pulse output terminal HDO can also be set to high-speed
pulse output or digital output by function code.
0
1
2
3
4
5
.
.
.
.
29
30
P06.01
P06.03
P06.04
P06.02
T delay
T delay
T delay
T delay
0
1
P06.05 output polarity
selection
(
Default value: 0
)
(
Default value: 0
)
(
Default value: 1
)
(
Default value: 5
)
P06.00
HDO
input type
0
1
0
1
0
1
delay
0
1
-1
-1
-1
-1
P17.13
Digital input
terminal state
P07.40
Digital output
terminal state
of current fault
Fault
?
Fault
Run
Y
BIT0
HDO
BIT1
ROI
BIT2
RO2
BIT3
P06.05, P17.13, P07.40 display
P06.00
0: Open collector high-
speed pulse output
1: Open collector output
P06.07
P06.09
P06.11
P06.13
Y
RO2
ROI
HDO
Digital switch-off delay
Digital output selection
T delay
T delay
T delay
T delay
delay
P06.06
P06.08
P06.10
P06.12
Digital switch-on delay
The following table lists the function code options. A same output terminal function can be repeatedly
selected.
Set
value
Function
Description
0
Invalid
Output terminal has no function
1
In running
Output ON signal when there is frequency output
during running
2
In forward running
Output ON signal when there is frequency output
during forward running
3
In reverse running
Output ON signal when there is frequency output
during reverse running
4
In jogging
Output ON signal when there is frequency output
during jogging
5
VFD fault
Output ON signal when VFD fault occurred
6
Frequency level detection FDT1
Refer to P08.32 and P08.33
7
Frequency level detection FDT2
Refer to P08.34 and P08.35
8
Frequency reached
Refer to P08.36