Goodrive350A series high-performance multifunction VFD
Function parameter list
-194-
Function
code
Name
Description
Default
Modify
automatic fault reset times is cleared.
Setting range of P08.28: 0
–10
Setting range of P08.29: 0.1
–3600.0s
P08.30
Frequency
decrease ratio in
drop control
The output frequency of the VFD changes as
the load changes. The function code is mainly
used to balance the power when several
motors drive a same load.
Setting range: 0.00
–50.00Hz
0.00Hz
○
P08.31
Channel for
switching between
motor 1 and motor 2
0x00
–0x14
Ones: Switchover channel
0: Switch over by terminal
1: Switch over by Modbus/Modbus TCP
communication
2: Switch over by
PROFIBUS/CANopen/DeviceNet
communication
3: Switch over by Ethernet communication
4: Switch over by
EtherCAT/PROFINET/EtherNet IP
communication
Tens: Motor switchover during running
0: Disable switchover during running
1: Enable switchover during running
0x00
◎
P08.32
FDT1 electrical
level detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical
level, the multifunction digital output terminal
continuously outputs the signal of "Frequency
level detection FDT". The signal is invalid only
when the output frequency decreases to a
value lower than the frequency corresponding
to (FDT electrical level
—FDT lagging
detection value).
50.00Hz
○
P08.33
FDT1 lagging
detection value
5.0%
○
P08.34
FDT2 electrical
level detection
value
50.00Hz
○
P08.35
FDT2 lagging
5.0%
○