Goodrive350A series high-performance multifunction VFD
Function parameter list
-169-
Function
code
Name
Description
Default
Modify
switching off IF
mode for AM 1
P04.45
Enabling IF mode
for AM 2
0: Disable
1: Enable
0
◎
P04.46
Current setting in IF
mode for AM 2
When IF control is adopted for AM 2, the
function code is used to set the output
current. The value is a percentage in relative
to the rated current of the motor.
Setting range: 0.0
–200.0%
120.0%
○
P04.47
Proportional
coefficient in IF
mode for AM 2
When IF control is adopted for AM 2, the
function code is used to set the proportional
coefficient of output current closed-loop
control.
Setting range: 0
–5000
650
○
P04.48
Integral coefficient
in IF mode for AM 2
When IF control is adopted for AM 2, the
function code is used to set the integral
coefficient of output current closed-loop
control.
Setting range: 0
–5000
350
○
P04.49
Frequency
threshold for
switching off IF
mode for AM 2
0.00Hz
–P04.51
10.00Hz
○
P04.50
End frequency point
for switching off IF
mode for AM 1
P04.44
–P00.03
25.00Hz
○
P04.51
End frequency point
for switching off IF
mode for AM 2
P04.49
–P00.03
25.00Hz
○
P05
—
Input terminals
Function
code
Name
Description
Default
Modify
P05.00
HDI input type
0x00
–0x11
Ones place: HDIA input type
0: HDIA is high-speed pulse input
1: HDIA is digital input
0x00
◎