Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-65-
Function
code
Name
Description
Default
closed-loop
proportional
coefficient in SM
V/F control
function code is used to set the proportional
coefficient of reactive current closed-loop
control.
Setting range: 0
–3000
Reactive current
closed-loop
integral time in SM
V/F control
When the SM V/F control mode is enabled, the
function code is used to set the integral
coefficient of reactive current closed-loop
control.
Setting range: 0
–3000
30
Reactive current
closed-loop output
limit in SM V/F
control
When the SM V/F control mode is enabled, the
function code is used to set the output limit of
the reactive current closed-loop control. A
greater value indicates a higher reactive
closed-loop compensation voltage and higher
output power of the motor. In general, you do
not need to modify the function code.
Setting range: 0
–16000
8000
Enabling IF mode
for AM 1
0: Disable
1: Enable
0
Current setting in
IF mode for AM 1
When IF control is adopted for AM 1, the
function code is used to set the output current.
The value is a percentage in relative to the
rated current of the motor.
Setting range: 0.0
–200.0%
120.0%
Proportional
coefficient in IF
mode for AM 1
When IF control is adopted for AM 1, the
function code is used to set the proportional
coefficient of the output current closed-loop
control.
Setting range: 0
–5000
650
Integral coefficient
in IF mode for AM
1
When IF control is adopted for AM 1, the
function code is used to set the integral
coefficient of the output current closed-loop
control.
Setting range: 0
–5000
350
Starting frequency
point for switching
off IF mode for AM
0.00
–P04.50
10.00Hz