Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-78-
(2)
Logic diagram for start after power-off restart is effective
Standby
The running state
before power cut
0
1
P01.21
(restart at power-cut)
Waiting time of restart at
power-cut>P01.22
0
1
2
Stop
Run
0
1
P01.18
(Power-on terminal running protection
selection)
Delay time of restart
>P01.123
N
Y
Y
N
Restart after
power-cut
Run
Stop
FWD/REV
Whether running terminal
command is valid
N
Run
Y
P00.01
Running command channel
Keypad
Communi
cation
Termin
al
(3)
Logic diagram for start after automatic fault reset
VFD fault
In running
Automatic reset times
of VFD fault<P08.28
Automatic reset
interval of VFD
fault>P08.29
VFD fault reset,
start running
Display fault
code, and stop
N
N
Y
Y
Related parameter list:
Function
code
Name
Description
Default
Channel of running
commands
0: Keypad
1: Terminal
2: Communication
0
ACC time 1
0.0
–3600.0s
Model
depended
DEC time 1
0.0
–3600.0s
Model
depended
Start mode
0: Direct start
1: Start after DC braking
2: Start after speedtracking
0
Starting frequency of direct
start
0.00
–50.00Hz
0.50Hz