Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-50-
Function
code
Name
Description
Default
the present motor is motor 1, only P02.06,
P02.07 and P02.08 are autotuned; when the
present motor is motor 2, only P12.06, P12.07
and P12.08 are autotuned.
4: Rotary autotuning 2, similar to rotary
autotuning 1, but valid only to AMs
5: Static autotuning 3 (partial autotuning), valid
only to AMs
Function
parameter restore
0: No operation
1: Restore default values (excluding motor
parameters)
2: Clear fault records
3: Reserved
4: Reserved
5: Restore default values (for factory test mode)
6: Restore default values (including motor
parameters)
Note:
After the selected operation is done, this
parameter is automatically restored to 0.
Restoring the default values may delete the user
password. Exercise caution when using this
function. The option 5 can be used only for
factory testing.
0
Type of motor 1
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
Rated power of
AM 1
0.1
–3000.0kW
Model
depended
Rated frequency
of AM 1
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
Rated speed of
AM 1
1
–60000rpm
Model
depended
Rated voltage of
AM 1
0
–1200V
Model
depended
Rated current of
AM 1
0.8
–6000.0A
Model
depended