Goodrive350A series high-performance multifunction VFD
Function parameter list
-157-
Function
code
Name
Description
Default
Modify
through keypad in
torque control
P03.18
Setting source of
electromotive
torque upper limit
0: Keypad (P03.20)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
5: Modbus/Modbus TCP communication
6: PROFIBUS/CANopen/DeviceNet
communication
7: Ethernet communication
8: Pulse frequency HDIB
9: EtherCAT/PROFINET/EtherNet IP
communication
10: Programmable card
11: Reserved
Note:
For these settings, 100% corresponds
to the motor rated current.
0
○
P03.19
Setting source of
braking torque
upper limit
0: Keypad (P03.21)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
5: Modbus/Modbus TCP communication
6: PROFIBUS/CANopen/DeviceNet
communication
7: Ethernet communication
8: Pulse frequency HDIB
9: EtherCAT/PROFINET/EtherNet IP
communication
10: Programmable card
11: Reserved
Note:
For these settings, 100% corresponds
to the motor rated current.
0
○
P03.20
Electromotive
torque upper limit
set through keypad
Used to set torque limits.
Setting range: 0.0
–300.0% (of the motor rated
current)
180.0%
○
P03.21
Braking torque
180.0%
○