Goodrive350A series high-performance multifunction VFD
Function parameter list
-249-
Function
code
Name
Description
Default
value
Modify
magnetic pole
angle autotuning
P21
—
Position control
Function
code
Name
Description
Default
value
Modify
P21.00 Positioning mode
0x0000
–0x7121
Ones: Control mode selection
0: Speed control
1: Position control
Tens: Position command source
0: Pulse strain
1: Digital position
2: Positioning of photoelectric switch during
stop
Hundreds: Position feedback source
(reserved, fixed to channel P)
0: PG1
1: PG2
Thousands: Servo mode (Reserved)
0: Servo disabled, without position deviation
1: Servo disabled, with position deviation
2: Servo enabled, without position deviation
3: Servo enabled, with position deviation
4
–7: Reserved
Note:
In pulse train positioning mode or
spindle positioning mode, when the servo
enabling signal is valid, the VFD enters the
servo running mode; when there is no servo
enabling signal, the VFD can use the servo
running mode only after receiving the FWD or
REV running mode.
0x0000
○
P21.01
Pulse command
mode
0x0000
–0x3133
Ones place: Pulse mode
0: A/B quadrature pulse; A leads B
1: A: PULSE; B: SIGN
If channel B is of low electric level, the edge
counts up; if channel B is of high electric level,
0x0000
◎