Goodrive350A series high-performance multifunction VFD
Function parameter list
-172-
Function
code
Name
Description
Default
Modify
63: Enable servo
64: Limit of forward run
65: Limit of reverse run
66: Zero out encoder counting
67: Pulse increase
68: Enable pulse superimposition
69: Pulse decrease
70: Electronic gear selection
71: Switch to master
72: Switch to slave
73: Reset the roll diameter
74: Switch winding/unwinding
75: Pre-drive
76: Disable roll diameter calculation
77: Clear alarm display
78: Manual braking
79: Trigger forced feeding interrupt
80: Initial roll diameter 1
81: Initial roll diameter 2
82: Trigger fire mode control
83: Switch tension PID parameters
84
–95: Reserved
P05.07
Reserved
P05.08
Input terminal
polarity
Used to set the polarity of input terminals.
When a bit is 0, the input terminal is positive;
when a bit is 1, the input terminal is negative.
0x000
–0x3F
0x00
○
P05.09
Digital input filter
time
Used to set the filter time for S1
–S4, HDIA,
and HDIB. In strong interference cases,
increase the value to avoid maloperation.
0.000
–1.000s
0.010s
○
P05.10
Virtual terminal
setting
0x00
–0x3F (0: disable, 1: enable)
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: HDIA virtual terminal
BIT5: HDIB virtual terminal
0x00
◎