2: Run at the frequency upper limit
3: Run at the frequency lower limit
4: Run at the frequency reserved for
exception
P11.52
Frequency reserved
for exception
0.00
–630.00Hz
0.00Hz
○
P11.53 Fire mode function
0
–2
0: Invalid
1: Fire mode 1
2: Fire mode 2
When P11.53=0, the fire mode is invalid, and
the normal running mode is used. In this case,
the VFD stops when encountering a fault.
When the fire mode function is valid, the VFD
runs at the speed specified by P11.54.
When fire mode 1 is selected, the VFD always
runs except when the VFD has been
damaged.
When fire mode 2 is selected, the VFD always
runs, but the VFD stops when encountering
OUT1, OUT2, OUT3, OC1, OC2, OC3, OV1,
OV2, OV3, or SPO.
Note:
Terminal control must be used for a fire
mode.
When the fire mode has lasted 5 minutes, it is
reset, and no warranty of repair is processed.
0
◎
P11.54
Running frequency
in fire mode
0.00Hz
–P00.03 (Max. output frequency)
50.00Hz
○
P11.55
Fire mode flag
0
–1
Note:
When the fire mode has lasted 5
minutes, it is reset, and no warranty of repair
is processed.
0
●