Goodrive350A series high-performance multifunction VFD
Function parameter list
-197-
Function
code
Name
Description
Default
Modify
1: Yes
P08.42
Reserved
P08.43
Reserved
P08.44
UP/DOWN terminal
control setting
0x000
–0x221
Ones place: Frequency setting selection
0: The setting made through UP/DOWN is
valid.
1: The setting made through UP/DOWN is
invalid.
Ones place: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: Valid for all frequency setting methods
2: Invalid for multi-step speed running when
multi-step speed running has the priority
Hundreds place: Action selection for stop
0: Setting is valid.
1: Valid during running, cleared after stop
2: Valid during running, cleared after a stop
command is received
0x000
○
P08.45
Frequency
increment integral
rate of the UP
terminal
0.01
–50.00Hz/s
0.50Hz/s
○
P08.46
Frequency integral
rate of the DOWN
terminal
0.01
–50.00Hz/s
0.50Hz/s
○
P08.47
Action selection at
power-off during
frequency setting
0x000
–0x111
Ones place: Action selection at power-off
during frequency adjusting through digitals.
0: Save the setting at power-off.
1: Clear the setting at power-off.
Action selection at power-off during frequency
adjusting through Modbus/ Modbus TCP
communication
0: Save the setting at power-off.
1: Clear the setting at power-off.
Hundreds place: Action selection at power-off
0x000
○