Goodrive350A series high-performance multifunction VFD
Function parameter list
-160-
Function
code
Name
Description
Default
Modify
speed-loop integral separation
0: Disable
1: Enable
Thousands place: Reserved
0: Reserved
1: Reserved
Range: 0x0000
–0x1111
P03.36
Speed-loop
differential gain
0.00
–10.00s
0.00s
○
P03.37
High-frequency
current-loop
proportional
coefficient
Under the FVC mode (P00.00=3), when the
frequency is lower than the current-loop
high-frequency switching threshold (P03.39),
the current-loop PI parameters are P03.09
and P03.10; and when the frequency is higher
than the current-loop high-frequency
switching threshold (P03.39), the current-loop
PI parameters are P03.37 and P03.38.
Setting range of P03.37: 0
–20000
Setting range of P03.38: 0
–20000
Setting range of P03.39: 0.0
–100.0% (of the
maximum frequency)
1000
○
P03.38
High-frequency
current-loop
integral coefficient
1000
○
P03.39
Current-loop
high-frequency
switching threshold
100.0%
○
P03.40
Enabling inertia
compensation
0: Disable
1: Enable
0
○
P03.41
Upper limit of inertia
compensation
torque
The max. inertia compensation torque is
limited to prevent inertia compensation torque
from being too large.
Setting range: 0.0
–150.0% (of the motor rated
torque)
10.0%
○
P03.42
Inertia
compensation filter
times
Filter times of inertia compensation torque,
used to smooth inertia compensation torque.
Setting range: 0
–10
7
○
P03.43
Inertia identification
torque value
Due to friction force, it is required to set
certain identification torque for the inertia
identification to be performed properly.
Setting range: 0.0
–100.0% (of the motor rated
torque)
10.0%
○
P03.44
Enabling inertia
0: No operation
0
◎