Goodrive350A series high-performance multifunction VFD
Installation guidelines
-17-
OK
NG
NG
A. Vertical installation
B. Horizontal installation
C. Transverse installation
Figure 4.1 Installation direction of the VFD
4.2.3 Installation mode
There are three kinds of installation modes based on different VFD dimensions.
Wall-mounting: suitable for 315G/355P and lower models
Flange-mounting: suitable for 200G/220P and lower models
Floor-mounting: suitable for 220G/250P
–500G models
Wall-mounting
Flange-mounting
Figure 4.2 Installation mode
(1) Mark the position of the installation hole. See appendix for the position of installation hole;
(2) Mount the screws or bolts onto the designated position;
(3) Put the VFD on the wall;
(4) Tighten the fixing screws on the wall.
Note:
The flange-mounting plate is a must for 1R5G/2R2P
–075G/090P models that adopt
flange-mounting mode; while 090G/110P
–200G/220P models need no flange-mounting plate.
The installation base is optional for 220G/250P
–315G/355P models. The base can hold an input
AC reactor (or DC reactor) and an output AC reactor.