Goodrive350A series high-performance multifunction VFD
Function parameter list
-175-
Function
code
Name
Description
Default
Modify
FWD
REV
COM
Sln
SB2
SB1
SB3
Sin
FWD
REV
Running
direction
ON
OFF→O
N
ON
Run
forward
OFF
Run
forward
ON
ON
OFF→ON
Run
reversely
OFF
Run
reversely
ON→
OFF
Decelerate
to stop
Sin: Three-wire control; FWD: Forward
running; REV: Reverse running
Note:
For two-wire controlled running mode,
when the FWD/REV terminal is valid, if the
VFD stops due to a stop command given by
another source, the VFD does not run again
after the stop command disappears even if
the control terminal FWD/REV is still valid. To
make the VFD run, you need to trigger
FWD/REV again, for example, PLC
single-cycle stop, fixed-length stop, and valid
STOP/RST stop during terminal control. (See
P07.04.)