Goodrive350A series high-performance multifunction VFD
Basic operation guidelines
-70-
Function
code
Name
Description
Default
6: PROFIBUS/CANopen/DeviceNet communication
7: Ethernet communication
8: Pulse frequency HDIB
9: EtherCAT/PROFINET/EtherNet IP
communication
10: Programmable card
11: Reserved
Note:
For these settings, 100% corresponds to the
motor rated current.
Setting source of
braking torque
upper limit
0: Keypad (P03.21)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
5: Modbus/Modbus TCP communication
6: PROFIBUS/CANopen/DeviceNet communication
7: Ethernet communication
8: Pulse frequency HDIB
9: EtherCAT/PROFINET/EtherNet IP
communication
10: Programmable card
11: Reserved
Note:
For these settings, 100% corresponds to the
motor rated current.
0
Electromotive
torque upper limit
set through
keypad
0.0
–300.0% (of the motor rated current)
180.0%
Braking torque
upper limit set
through keypad
0.0
–300.0% (of the motor rated current)
180.0%
Output torque
-250.0
–250.0%
0.0%
Torque reference
value
-300.0
–300.0% (of the motor rated current)
0.0%
5.5.6 Motor parameters
Check the safety conditions surrounding the motor and load machineries before
autotuning as physical injury may occur due to sudden start of motor during