Goodrive350A series high-performance multifunction VFD
Function parameter list
-166-
Function
code
Name
Description
Default
Modify
P04.25
Oscillation control
threshold of motor 2
eliminate such phenomenon.
Setting range of P04.23: 0
–100
Setting range of P04.24: 0
–100
Setting range of P04.25: 0.00Hz
(Max. output frequency)
30.00Hz
○
P04.26
Energy-saving run
0: Disable
1: Automatic energy-saving run
In light-load state, the motor can adjust the
output voltage automatically to achieve
energy saving.
0
◎
P04.27
Voltage setting
channel
0: Keypad (The output voltage is determined
1: AI1
2: AI2
3: AI3
4: HDIA
5: Multi-step speed running (The setting is
determined by group P10.)
6: PID
7: Modbus/Modbus TCP communication
8: PROFIBUS/CANopen/DeviceNet
communication
9: Ethernet communication
10: HDIB
11: EtherCAT/PROFINET/EthernetIP
communication
12: Programmable card
13: Reserved
0
○
P04.28
Voltage set through
keypad
The function code is the voltage digital setting
when "keypad” is selected as the voltage
setting channel.
Setting range: 0.0%
–100.0%
100.0%
○
P04.29
Voltage increase
time
Voltage increase time means the time needed
for the VFD to accelerate from min. output
voltage to the max. output frequency.
Voltage decrease time means the time
needed for the VFD to decelerate from the
max. output frequency to min. output voltage.
5.0s
○
P04.30
Voltage decrease
time
5.0s
○