Goodrive350A series high-performance multifunction VFD
Function parameter list
-223-
Function
code
Name
Description
Default
value
Modify
reports the "Modbus/Modbus TCP
communication fault" (CE) if the
communication interval exceeds the value.
In general, this parameter is set to 0.0. When
continuous communication is required, you
can set the function code to monitor
communication status.
P14.05
Transmission error
processing
0: Report an alarm and coast to stop
1: Keep running without reporting an alarm
2: Stop in enabled stop mode without
reporting an alarm (applicable only to
communication mode)
3: Stop in enabled stop mode without
reporting an alarm (applicable to any mode)
0
○
P14.06
Modbus
communication
processing action
0x000
–0x111
Ones:
0: Write operation has response
1: Write operation has no response
Tens:
0: Communication password protection is
invalid
1: Communication password protection is
valid
Hundreds place: Valid only for RS485
communication
0: User-defined addresses specified by
P14.07 and P14.08 are invalid
1: User-defined addresses specified by
P14.07 and P14.08 are valid
0x000
○
P14.07
User-defined
running command
address
0x0000
–0xFFFF
0x2000
○
P14.08
User-defined
frequency setting
address
0x0000
–0xFFFF
0x2001
○
P14.09
Modbus TCP
communication
timeout time
0.0
–60.0s
5.0s
○