MC1000 FAULT HISTORY
Parameter 70 - FAULT HISTORY stores the last eight faults that tripped
the drive. The FAULT HISTORY indicates the number of the fault
(number 1 is the most recent fault), the fault message, and the status of
the drive at the time of the fault. An example is shown below:
MC1000 FAULT MESSAGES
FAU
LT
DES
CRIP
TION
OUTPUT
LO VOLTS
HI VOLTS
HI TEMP
OVERLOAD
PWR TRAN
PWR SAG
LANGUAGE
EXTERNAL
DB ERROR
CONTROL
INTERNAL
INTERN (#)
Output Transistor fault; Output current exceeded
200%. May be ground fault or short circuit.
Low DC Bus Voltage fault: DC bus voltage
dropped below 60%. May be low line voltage.
High DC Bus Voltage fault: DC bus voltage
exceeded 120%. May be overhauling load.
High Temperature fault: Heatsink or ambient
temperature too high.
Current Overload fault: Output current exceeded
100% for too long. VFD may be undersized.
Power Transient fault.
Power Sag fault: New control board installed.
Perform factory reset using Parameter 65.
Language EEPROM fault.
External fault: TB-13D activated (Parameter 50).
Dynamic Brake fault: DB Resistors overloaded.
Control Board fault: New software installed.
Perform factory reset using Parameter 65.
Internal fault.
Internal fault.
In the example above, the second fault is being viewed, which is an
OUTPUT fault that ocurred while the drive was accelerating.
2 OUTPUT ACCEL
FAULT
NUMBER
FAULT
MESSAGE
DRIVE
STATUS
MC1000 PARAMETERS
QRM1-OBOC
NOTE 1: REFER TO THE MC1000 MANUAL.
NOTE 2: THESE PARAMETERS ARE VIEW-ONLY.
AC Technology Corporation
660 Douglas St, Uxbridge, MA 01569
800-217-9100, FAX: 508-278-7873
www.actechdrives.com
NOTE:
Before installing and operating the MC1000 drive,
please read and become familiar with the MC1000 Series
Installation and Operation Manual.
MC1000 Series
Quick Reference Guide
RUN > 60.00 HZ
Intelligent Drive
START
STOP
ENTER
AUTO
MAN
PROG
RUN
FWD
REV
CONTROL
LOCAL
30
FAULT
HISTORY
(NOTE 2)
70
UNITS
HERTZ
31
SPEED DP
XXXXX
33
LOAD MLT
100 %
34
SPEED #4
20.00 HZ
4
SPEED #3
20.00 HZ
3
SPEED #2
20.00 HZ
2
SPEED #1
20.00 HZ
1
LINE VOLTS
AUTO
0
HZ MULT
1.00
32
SKIP #1
.00 HZ
5
SKIP #2
.00 HZ
6
BAND WID
1.00 HZ
7
TB5 MAX
60.00 HZ
40
ACCEL
30.0 SEC
8
AIN FLTR
0.02 SEC
41
DECEL
30.0 SEC
9
TB10A OUT
NONE
42
MIN FRQ
.50 HZ
10
@TB10A
60.00 HZ
43
MAX FRQ
60.00 HZ
11
TB10B OUT
NONE
44
DC BRAKE
.0 VDC
12
@TB10B
125 %
45
DC TIME
.0 SEC
13
TB13A
NONE
47
DYN BRAKE
OFF
14
TB13B
NONE
48
CURRENT
180 %
16
TB13C
NONE
49
MOTOR OL
100 %
17
TB13D
EXT FAULT
50
BASE
60.00 HZ
18
TB14 OUT
NONE
52
FX BOOST
(NOTE 1)
19
TB15 OUT
NONE
53
AC BOOST
.0 %
20
RELAY
NONE
54
SLIP CMP
.0 %
21
SERIAL
DISABLE
57
TORQUE
CONSTANT
22
ADDRESS
30
58
CARRIER
2.5 KHZ
23
PASSWORD
0019
61
START
NORMAL
25
SOFTWARE
(NOTE 2)
63
STOP
COAST
26
MONITOR
ON
64
ROTATION
FORWARD
27
PROGRAM
RESET 60
65
AUTO / MAN
BOTH
28
HISTORY
MAINTAIN
66
MANUAL
KEYPAD
29
LANGUAGE
ENGLISH
69
CONTRAST
MED
35
SLEEP TH
.00 HZ
36
SLEEP DL
30.0 SEC
37
TB5 MIN
.00 HZ
39
PARAMETER
NAME
FACTORY
DEFAULT
NO.
PARAMETER
NAME
FACTORY
DEFAULT
NO.