Goodrive350A series high-performance multifunction VFD
Communication
-324-
Note:
Sections 9.4.1 and 9.4.2 mainly describe the command formats. For the detailed application,
see section 9.4.8.
9.4.3 Command code 08H, diagnosis
Sub-function code description:
Sub-function code
Description
0000
Return data based on query requests
For example, to query about the circuit detection information about the VFD whose address is 01H,
the query and return strings are the same, and the formats are described in the following tables.
RTU master command:
START
T1-T2-T3-T4 (time gap with a min. length
of 3.5 bytes)
ADDR
01H
CMD
08H
Sub-function code high-order bit
00H
Sub-function code low-order bit
00H
Data content high-order bit
12H
Data content low-order bit
ABH
CRC CHK low-order bit
ADH
CRC CHK high-order bit
14H
END
T1-T2-T3-T4 (time gap with a min. length
of 3.5 bytes)
RTU slave response:
START
T1-T2-T3-T4 (time gap with a min. length of
3.5 bytes)
ADDR
01H
CMD
08H
Sub-function code high-order bit
00H
Sub-function code low-order bit
00H
Data content high-order bit
12H
Data content low-order bit
ABH
CRC CHK low-order bit
ADH
CRC CHK high-order bit
14H
END
T1-T2-T3-T4 (time gap with a min. length of
3.5 bytes)
9.4.4 Command code 10H, continuous writing
The command code 10H is used by the master to write data to the VFD. The quantity of data to be